What happens on a 50,000 Btu/h morning?
At 5°F the Carrier delivers 53,500 Btu/h of heat at a COP of 1.90. The Trane delivers 48,000 Btu/h at a COP of 2.05. If a load calculation puts the house at 50,000 Btu/h at 5°F, the Carrier has 3,500 Btu/h to spare on the rating. The Trane would need help with the last 2,000 Btu/h. In a house where both cover the load, the Trane’s higher COP at this temperature implies less electricity per unit of heat.
What backup heat is included?
The Carrier rating lists a 59TN7A100C21**22 furnace with the indoor coil. The Trane lists a 5TEMCD07BV51+TDR indoor combination. Have each installer identify the backup on the bid and its control settings. If the furnace takes over before the outdoor temperature reaches 5°F, the gas price and furnace efficiency will matter more on that morning than the Carrier’s heat pump rating.
Specifications side by side
Figures apply to the equipment combinations shown. N/A marks a field that is missing or does not apply.
| Specification | Carrier 27VNA154A*030* | Trane 5TCV0X60A1 |
|---|---|---|
| System type | Split heat pump | Split heat pump |
| Outdoor / packaged model | 27VNA154A*030* | 5TCV0X60A1 |
| Indoor model | CSAH*6012AM*+UI | 5TEMCD07BV51+TDR |
| Furnace in this rating | 59TN7A100C21**22 | N/A |
| AHRI reference | 215588461 | 218792279 |
| EPA product ID | 3719788 | 4704986 |
| Compressor staging | Variable-speed | Variable-speed |
| Refrigerant | R-454B | R-454B |
| Cooling capacity | 49,500 Btu/h | 48,500 Btu/h |
| SEER2 | 18.5 | 19.2 |
| EER2 | 11.5 | 11.5 |
| HSPF2 | 9.5 | 9.4 |
| Heat at 47°F | 52,500 Btu/h | 55,000 Btu/h |
| Heat at 17°F | 50,500 Btu/h | 44,000 Btu/h |
| Heat at 5°F | 53,500 Btu/h | 48,000 Btu/h |
| COP at 5°F | 1.9 | 2.05 |