Rated equipment configuration

York YDV60E2D11 · rating 218450370

The published rating for this configuration lists 52,000 Btu/h of cooling. Check the indoor model JDE60F5XX2DS1 against your proposal.

Equipment on the rating

System type
Split heat pump
Outdoor / packaged model
YDV60E2D11
Indoor model
JDE60F5XX2DS1
Furnace in this rating
N/A
AHRI reference
218450370
EPA product ID
4624094
Compressor staging
Variable-speed
Refrigerant
R-454B
Cooling capacity
52,000 Btu/h
SEER2
18
EER2
11.7
HSPF2
9.5
Heat at 47°F
55,000 Btu/h
Heat at 17°F
44,000 Btu/h
Heat at 5°F
38,500 Btu/h
COP at 5°F
2

What the numbers mean

For each million Btu of seasonal cooling, the published SEER2 works out to 55.6 kWh.

At the published 5°F test point, the system delivers 38,500 Btu/h. Compare that with the heating load at the same temperature.

At 5°F the unit delivers 70% of its listed 47°F heating output (38,500 versus 55,000 Btu/h).

Seasonal cooling electricity55.6kWh per million Btu56/100Score 56 / 100
Peak cooling power1.03kW per ton at the EER2 test point78/100Score 78 / 100
Seasonal heating electricity105.3kWh per million Btu74/100Score 74 / 100
Heating electricity at 5°F146.5kWh per million Btu at 5°F46/100Score 46 / 100

Scores compare published readings within this equipment type in our catalog. Lower electricity use earns a higher score. See the formulas.

Source record

Check the source record for model wildcards. A listed furnace is part of the rated combination whenever the source names one.