HVAC MatchupQuote worksheet

Rated equipment configuration

Bryant 290VAN036**AA* · rating 215684030

The published rating for this configuration lists 33,600 Btu/h of cooling. Check the indoor model CSAH*3612AM*+UI against your proposal.

Equipment on the rating

System type
Split heat pump
Outdoor / packaged model
290VAN036**AA*
Indoor model
CSAH*3612AM*+UI
Furnace in this rating
935CB48060C17***
AHRI reference
215684030
EPA product ID
3716601
Compressor staging
Variable-speed
Refrigerant
R-454B
Cooling capacity
33,600 Btu/h
SEER2
16
EER2
9
HSPF2
8.5
Heat at 47°F
35,800 Btu/h
Heat at 17°F
31,000 Btu/h
Heat at 5°F
25,600 Btu/h
COP at 5°F
1.76

What the numbers mean

For each million Btu of seasonal cooling, the published SEER2 works out to 62.5 kWh.

At the published 5°F test point, the system delivers 25,600 Btu/h. Compare that with the heating load at the same temperature.

At 5°F the unit delivers 72% of its listed 47°F heating output (25,600 versus 35,800 Btu/h).

The rating includes furnace 935CB48060C17***. Ask for the rating of the new combination if the proposal keeps another furnace.

Seasonal cooling electricity62.5kWh per million Btu18/100Score 18 / 100
Peak cooling power1.33kW per ton at the EER2 test point18/100Score 18 / 100
Seasonal heating electricity117.6kWh per million Btu34/100Score 34 / 100
Heating electricity at 5°F166.5kWh per million Btu at 5°F2/100Score 2 / 100

Scores compare published readings within this equipment type in our catalog. Lower electricity use earns a higher score. See the formulas.

Source record

Check the source record for model wildcards. A listed furnace is part of the rated combination whenever the source names one.